Connections
- Lumcove modules work at mains voltage 220-240V
- Ideally the mains cable should be entered into the cove at either 15 cm from the corner or at 15cm from the cove end
1. Lumcove with fixed luminous flux (without dimming)
- Power cable with 3 wires
- Power supply: 3x1,5mm² (bleu, brown, green/earthing)
The table below shows how many Lumcove modules can be connected to one power cable:
C: circuit breaker for slow switch-off (5 to 10 In)
B: circuit breaker for fast switch-off (3 to 5 In) with 10A and 16A
| Maximum number of modules for 1 power cable |
| Module type-Wattage | C10
1,5mm² | C16
1,5mm² | B10
1,5mm² | B16
1,5mm² |
| 35 | 46 | 80 | 23 | 40 |
| 28 | 44 | 80 | 22 | 40 |
| 21 | 46 | 86 | 23 | 43 |
2. Lumcove with variable luminous flux (with dimming)
- Power cable with 5 wires
- Power supply: 3x1,5mm² (bleu, brown, green/earthing)
- dimming: 2x0,5mm² (red+, black-) (or 5x1,5mm²)
The table below shows how many Lumcove modules can be connected to one power cable:
C: circuit breaker for slow switch-off (5 to 10 In)
B: circuit breaker for fast switch-off (3 to 5 In) with 10A and 16A
| Maximum number of modules for 1 power cable |
| Module type (D)-Wattage | C10
1,5mm² | C16
1,5mm² | B10
1,5mm² | B16
1,5mm² |
| 35 | 34 | 62 | 17 | 31 |
| 28 | 34 | 62 | 17 | 31 |
| 21 | 34 | 64 | 17 | 32 |